Siemens SIMATIC S7-200 System Manual page 432

Programmable controller
Hide thumbs Also See for SIMATIC S7-200:
Table of Contents

Advertisement

S7-200 Programmable Controller System Manual
Configuration for EM 235
Table A-22 shows how to configure the EM 235 module using the configuration DIP switches.
Switches 1 through 6 select the analog input range and resolution. All inputs are set to the same
analog input range and format. Table A-22 shows how to select for unipolar/bipolar (switch 6), gain
(switches 4 and 5), and attenuation (switches 1, 2, and 3). In these tables, ON is closed, and OFF
is open. The switch settings are read only when the power is turned on.
Table A-22
EM 235 Configuration Switch Table to Select Analog Range and Resolution
SW1
SW2
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
SW1
SW2
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
418
Unipolar
SW3
SW4
SW5
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Bipolar
SW3
SW4
SW5
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
Full Scale Input
Full-Scale Input
SW6
ON
0 to 50 mV
ON
0 to 100 mV
ON
0 to 500 mV
ON
0 to 1 V
ON
0 to 5 V
ON
0 to 20 mA
ON
0 to 10 V
Full-Scale Input
Full Scale Input
SW6
OFF
+25 mV
OFF
+50 mV
OFF
+100 mV
OFF
+250 mV
OFF
+500 mV
OFF
+1 V
OFF
+2.5 V
OFF
+5 V
OFF
+10 V
Resolution
Resolution
12.5 mV
25 mV
125 mV
250 mV
1.25 mV
5 mA
2.5 mV
Resolution
Resolution
12.5 mV
25 mV
50 mV
125 mV
250 mV
500 mV
1.25 mV
2.5 mV
5 mV

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents