S7-200 Programmable Controller System Manual
Table A-1
Technical Specifications
EN 60068--2--2, Test Bb, Dry heat and
EN 60068--2--1, Test Ab, Cold
EN 60068--2--30, Test Db, Damp heat
EN 60068--2--14, Test Na, Temperature Shock
EN 60068--2--32, Free fall
Ambient Temperature Range
(Inlet Air 25 mm below unit)
Atmospheric pressure
Concentration of contaminants
EN 60068--2--14, Test Nb, Temperature
change
EN 60068--2--27 Mechanical shock
EN 60068--2--6 Sinusoidal vibration
EN 60529, IP20 Mechanical protection
EN 61000--4--2 Electrostatic discharge
EN 61000--4--3 Radiated electromagnetic field
EN 61000--4--4 Fast transient bursts
EN 61000--4--5 Surge immunity
EN 61000--4--6 Conducted disturbances
EN 61000--4--11 Voltage dips, short
interruptions and voltage variations
VDE 0160 Non-periodic overvoltage
394
Environmental Conditions — Transport and Storage
--40° C to +70° C
25° C to 55° C, 95% humidity
--40° C to +70° C dwell time 3 hours, 2 cycles
0.3 m, 5 times, product packaging
Environmental Conditions — Operating
0° C to 55° C horizontal mounting, 0° C to 45° C vertical mounting
95% non-condensing humidity
1080 to 795 hPa (Corresponding to an altitude of --1000 to 2000 m)
S0
: < 0.5 ppm; H
2
5° C to 55° C, 3° C/minute
15 G, 11 ms pulse, 6 shocks in each of 3 axis
Panel mount:
DIN rail mount:
Protects against finger contact with high voltage as tested by standard probes.
External protection is required for dust, dirt, water, and foreign objects of < 12.5 mm in
diameter.
Electromagnetic Compatibility — Immunity per EN61000- -6- -2
8 kV air discharge to all surfaces and communications port,
4 kV contact discharge to exposed conductive surfaces
10 V/m from 80--1000 MHz, 80% AM at 1kHz
3 V/m from 1.4--2.0 GHz, 80% AM at 1kHz
1 V/m from 2.0--2.7 GHz, 80% AM at 1kHz
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to I/O
1 kV, 5 kHz with coupling clamp to communications
Power supply:
0.15 to 80 MHz, 10 V RMS, 80% AM at 1kHz
Residual voltage: 0% for 1 cycle, 40% for 12 cycles and 70% for 30 cycles @ 60Hz
voltage jump at zero crossing
At 85 VAC line, 90° phase angle, apply 390 V peak, 1.3 ms pulse
At 180 VAC line, 90° phase angle, apply 750 V peak, 1.3 ms pulse
S: < 0.1 ppm; RH < 60% non-condensing
2
7.0 mm from 5 to 9 Hz; 2 G from 9 to 150 Hz
3.5 mm from 5 to 9 Hz; 1 G from 9 to 150 Hz
10 sweeps each axis, 1 octave/minute
3
3
2 kV asymmetrical, 1 kV symmetrical
I/O 1 kV symmetrical
(24 VDC circuits require external surge protection)
1