UM353-1B

10.4.2 On-Line Error Codes and Status Codes

These codes can be produced while the controller is running function block and may be actively controlling a
process. Depending on the message and its priority level, user intervention may be required or the message may
simply be informational in nature. Parameter "SE" located at Modbus register $40002 will reflect unacknowledged
error or status messages present in the controller. Messages are displayed according to priority until all active
messages have been acknowledged. If no link code has been assigned to the active message, the "SE" code will
remain at its last value.
Table 10-2 lists on-line error and status codes. For most error codes, replace the involved circuit board to repair the
controller. For most status codes, acknowledge or otherwise respond to the situation.
DISPLAYED
LINK/MODBUS
CODE
CODE (Hex/Dec)
MPU A/D
$0001
EXP A/D
$0002
AOUT1 OC
$0003
AOUT2 OC
$0004
AOUT3 OC
$0005
AINU1 AD
$0006
AINU1 TC
$0007
AINU1 RJ
$0008
AINU2 AD
$0009
AINU2 TC
$000A
AINU2 RJ
$000B
UDIN E1
$000C
UDIN E2
$000D
MOD ERR
$0010
Watchdog
$0013
LOW BAT
$0014
MMC MEM
$0015
CYCLTIME
$0016
BURNFAIL
$0017
NO EXPBD
$0019
MB OVRUN
$001C
A1 HI
None
A1 LO
None
A1 HI D
None
A1 LO D
None
A1 DEV
None
A1 OR
None
A2 HI
None
A2 LO
None
A2 HI D
None
A2 LO D
None
A2 DEV
None
A2 OR
None
A3 HI
None
A3 LO
None
A3 HI D
None
A3 LO D
None
April 2012
Table 10-2 On-Line Error and Status Codes
DESCRIPTION
1
MPU Controller board A/D Error
2
I/O Expander Board A/D Error
3
MPU Controller board D/A #1 Open Circuit
4
MPU Controller board D/A #2 Open Circuit
5
MPU Controller board D/A #3 Open Circuit
6
I/O Expander Board Universal Analog Input #1 A/D Error
7
I/O Expander Board Universal Analog Input #1 T/C Burnout
8
I/O Expander Board Universal Analog Input #1 Reference Junction Error
9
I/O Expander Board Universal Analog Input #2 A/D Error
10
I/O Expander Board Universal Analog Input #2 T/C Burnout
11
I/O Expander Board Universal Analog Input #1 Reference Junction Error
12
I/O Expander Board Universal Digital Input #1 Underflow Error
13
I/O Expander Board Universal Digital Input #2 Underflow Error
16
Modbus Port Error
19
Watchdog Timeout
20
Low NVRAM Battery Voltage
21
Press STORE to load MMC configuration into MPU memory
22
Cycle Time Overrun – see STATN block – add Cycle Time bias
23
Flash Memory burn failed
25
Expander board is not installed
28
Modbus communication error
Alarm A1 High
Alarm A1 Low
Alarm A1 High Deviation
Alarm A1 Low Deviation
Alarm A1 Deviation
Alarm A1 Overrange
Alarm A2 High
Alarm A2 Low
Alarm A2 High Deviation
Alarm A2 Low Deviation
Alarm A2 Deviation
Alarm A2 Overrange
Alarm A3 High
Alarm A3 Low
Alarm A3 High Deviation
Alarm A3 Low Deviation
Maintenance