Siemens SIMATIC S7-200 System Manual page 467

Programmable controller
Hide thumbs Also See for SIMATIC S7-200:
Table of Contents

Advertisement

Table A-53
EM 253 Position Module Specifications, continued
General
Output Features
Number of integrated outputs
Output type
P0+, P0- -, P1+, P1- -
P0, P1, DIS, CLR
Output voltage
P0, P1, RS- -422 drivers, differential output voltage
Open circuit
Into optocoupler diode with 200Ω series resistance
100Ω load
54Ω load
P0, P1, DIS, CLR open drain
recommended voltage, open circuit
permissible voltage, open circuit
Sink current
On state resistance
Off state leakage current, 30 VDC
Internal Pull up resistor, output drain to T1
Output current
Number of output groups
Outputs on simultaneously
Leakage current per point
P0, P1, DIS, CLR
Overload Protection
Isolation (field to logic)
Optical Isolation (Galvanic)
Output delay
DIS, CLR: Off to On / On to Off
Pulse distortion
P0, P1, outputs, RS- -422 drivers, 100 Ω external
load
P0, P1 outputs, open drain, 5 V / 470 Ω external
load
Switching frequency
P0+, P0- -, P1+, P1- -, P0 and P1
Cable length
Unshielded
Shielded
Power Supply
L+ supply voltage
Logic supply output
L+ supply current vs. 5 VDC load
L
l
t
5 VDC l
d
Load current
0 mA (no load)
200 mA (rated load)
Isolation
L+ power to logic
L+ power to inputs
L+ power to outputs
Reverse Polarity
1
Operation of open drain outputs above 5 VDC may increase radio frequency emissions above permissible limits. Radio frequency containment measures
may be required for your system or wiring.
2
Depending on your pulse receiver and cable, an additional external pull up resistor may improve pulse signal quality and noise immunity.
6ES7 253- - 1AA22- - 0XA0
6 points (4 signals)
RS422/485 driver
Open drain
3.5 V typical
2.8 V minimum
1.5 V minimum
1.0 V minimum
5 VDC, available from module
1
30 VDC
50 mA maximum
15Ω maximum
10 µA maximum
2
3.3K Ω
1
All at 55° C (horizontal), All at 45° C (vertical)
10 µA maximum
No
500 VAC for 1 minute
30 µs, maximum
75 ns maximum
300 ns maximum
200 kHz
Not recommended
10 meters
11 to 30 VDC (Class 2, Limited Power, or sensor power from PLC)
+5 VDC +/- - 10%, 200 mA maximum
12 VDC Input
120 mA
300 mA
500 VAC for 1 minute
500 VAC for 1 minute
None
L+ input and +5V output are diode-protected. Placing a positive voltage on any M
terminal with respect to output point connections can result in potentially damaging
current flow.
Technical Specifications
24 VDC Input
70 mA
130 mA
Appendix A
453

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents