(Cp 243--2) As--Interface Module Specifications - Siemens SIMATIC S7-200 System Manual

Programmable controller
Hide thumbs Also See for SIMATIC S7-200:
Table of Contents

Advertisement

(CP 243- -2) AS- -Interface Module Specifications
Table A-64
(CP 243- -2) AS-Interface Module Order Number
Order Number
6GK7 243- -2AX01- -0XA0
Table A-65
(CP 243- -2) AS-Interface Module General Specifications
Order Number
6GK7 243- -2AX01- -0XA0
Table A-66
(CP 243- -2) AS-Interface Module Specifications
General
Cycle time
Configuration
AS- -I master profiles supported
Attachment to the AS- -I cable
Address range
Features
You can operate up to two AS--Interface modules on the S7-200 at the same time, significantly
increasing the number of available digital and analog inputs/outputs (maximum 124 digital
input/124 digital output on AS--Interface per CP). Setup times are reduced because of the ability to
configure at the touch of a button. LEDs reduce downtime in the event of an error by displaying
status of the CP and of all connected slaves, and by monitoring AS--Interface main voltage.
The AS--Interface Module has the following features:
Supports analog modules
-
Supports all master functions and allows connections for up to 62 AS--Interface slaves
-
LEDs in the front plate display operating status and availability of connected slaves.
-
LEDs in the front plate display errors (including AS--Interface voltage error, configuration
-
error)
Two terminals allow direct connection of the AS--Interface cable.
-
Two buttons display the status information of the slaves, switch operating mode, and adopt
-
the existing configuration as the SET configuration.
You can use the STEP 7--Micro/WIN AS-i Wizard to configure the (CP 243--2) AS--Interface
module. The AS--Interface Wizard helps you use the data from an AS-Interface network in your
configuration. To start the AS--i Wizard, select the Tools > AS- -i Wizard menu command.
AS-i
Expansion Model
(CP 243- -2) AS- -Interface Module
Module Name and
Dimensions (mm)
Description
(W x H x D)
(CP 243- -2) AS- -Interface
71 x 80 x 62
Module
5 ms with 31 slaves
10 ms with 62 AS- -I slaves using the extended addressing mode
Set button on the front panel, or use the total configuration command (refer to the
description of the AS- -I commands in the CP 243- -2 AS- -I Interface Master manual)
M1e
Via an S7-200 terminal block. Permitted current loading from terminal 1 to 3 or from
terminal 2 to 4 maximum 3 A.
One digital module with 8 digital inputs and 8 digital outputs, and
One analog module with 8 analog inputs and 8 analog outputs
Technical Specifications
EM Inputs
EM Outputs
8 Digital and 8 Analog
8 Digital and8 Analog
Weight
Dissipation
approx.
3.7 W
250 g
6GK7 243- - 2AX01- - 0XA0
Appendix A
Removable Connector
Yes
VDC Requirements
+5 VDC
From
AS- - Interface
220 mA
100 mA
463