Omron POWLI BU60RE Instruction Manual page 59

Uninterruptible power supply
Table of Contents

Advertisement

* When connecting 2 or more computers to the UPS (Only when using PowerAct Pro)
Power cable
PC server 3
Power cable
PC server 2
Power cable
PC server 1
Remote connection
The Included connection cable (RS-232C)
2. Install the included "PowerAct Pro 4.x/3.x" or "Simple Shutdown Software"
to the PC you want to shutdown.
Installation method:
Refer to the "Quick Installation Guide for UPS Monitoring Software" for "PowerAct Pro 4.x/3.x".
Refer to the manual in the CD-ROM for "Simple Shutdown Software."
Scheduled operation using the UPS monitoring software
When performing scheduled operation in which the UPS is stopped and a device such as a breaker is
used to stop the UPS at the same time that commercial power stops, specify a period of no more than
3 months for the start of the next operation.
If you specify a period longer than 3 months, the internal timer is reset and the scheduled operation
does not start.
Note that this period reduces to approximately half when the battery is dead.
If a period of 3 months is exceeded, you start operation by supplying commercial power and pressing
the Start Switch. However, if the battery is dead, you may not be able to start operation. In this case,
replace the battery according to "6-2 Replacing the battery" on page 39.
Start of operation in scheduled operation using the UPS monitoring software
To manually start up this unit after it has been stopped by a scheduled operation, turn OFF the power
switch and turn it back ON again.
To stop the unit when it is in operation, turn OFF the power switch.
Auto restart after OS closing processing using the UPS monitoring software
When a power failure occurs, certain PCs (*1) automatically restart immediately after the OS is shut
down by auto shutdown.
In this case, the UPS stops during or after the restart of the PC, which may damage fi les and the hard
disk. You can avoid this phenomenon by disabling POWER MANAGEMENT in the BIOS settings of the
PC.
*1) Certain PC: It is known that this phenomenon occurs for MICRON's Millennia Mme.
Precautions when "setting the UPS to stop automatically" after OS shutdown
If, after a power failure occurs, the power is restored while auto shutdown processing is being per-
formed, UPS output stops once after the set time elapses. After shutdown processing is complete, do
not turn ON the computer until the UPS has fi nished restarting.
Power cable
LAN connection
Network
Explanation
60
BU
RE/BU
Switching hub
100
RE
7
47