Synchronous/asynchronous operation setting (setting switch
... Factory setting: Refer to the table below.
Setting switch
Setting switch
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF,
OFF: Commercial synchronous operation (ECO mode disabled)
- Output voltage: Inverter output in Commercial Power Mode. It is not affected by
input voltage.
- Output frequency: Output in synchronization with input frequency.
- Bypass output: Bypass output in the event of failure or overload.
OFF,
ON: Commercial synchronous operation (ECO mode enabled)
- Output voltage: Input voltage is output as it is in Commercial Power Mode.
(Low power consumption due to bypass output). Input voltage is output as it is.
- Output frequency: The same as the input frequency due to normally bypass
output in Commercial Power Mode.
- When ECO mode enabled, the bypass output if age is within the range of "the
rated input voltage ± 10%."
ON,
OFF: Asynchronous operation (50 Hz output)
- Output voltage: Inverter output in Commercial Power Mode. It is not affected by
input voltage.
- Output frequency: Always output with 50 Hz. It is not affected by input
frequency.
- Bypass output: An output stops without bypass output in the event of failure or
overload.
ON,
ON:
Asynchronous operation (60 Hz output)
- Output voltage: Inverter output in Commercial Power Mode. It is not affected by
input voltage.
- Output frequency: Always output with 60 Hz. It is not affected by input
frequency.
- Bypass output: An output stops without bypass output in the event of failure or
overload.
ON
1
2
3
4
5
6
7
Operating mode
Commercial synchronous operation
(ECO mode disabled)
Commercial synchronous operation
(ECO mode enabled)
Asynchronous operation
(50 Hz output)
Asynchronous operation
(60 Hz output)
60
BU
DIP
8
100
RE/BU
RE
,
)
4
31