Auto startup mode setting (setting switch
OFF: (Mode A)
After UPS stopped, the UPS is automatically started immediately when "ON" is
detected for the AC input.
ON: (Mode B)
After UPS stopped, the UPS is automatically started in the AC input's "OFF to
ON" timing that is detected.
* Setting switch 4 is valid when the auto startup after recovery from power failure setting (setting
switch 2) is set to OFF (auto restart is performed).
* This setting mode is valid only after the UPS has been stopped by the contact signal backup
stop signal (BS).
* When a cable is connected to the RS-232C connector and the UPS monitoring software is used,
the unit operates in Mode A regardless of this setting.
(1) When BS signal is used to stop the UPS after a power failure occurs.
ON
AC input
OFF
ON
BS signal
OFF
ON
Power output
(Setting switch 4 OFF:
OFF
Mode A)
Power output
ON
(Setting switch 4 ON:
Mode B)
OFF
ON
1
2
3
4
5
(Defi nition of AC input OFF: When AC input is OFF for 1 second or more)
*1
) ... Factory setting: OFF
DIP
6
7
8
60