3) Signal input/output test (BL/TR/BU/WB/BS/remote)
Four types of output signal can be forcibly turned ON.
The ON/OFF state of two types of input signal can be checked with the status indicator
and the beeper.
Battery Low signal (BL)
(Between pins 1 and 5)
Trouble signal (TR)
(Between pins 2 and 5)
Backup signal (BU)
(Between pins 8 and 5)
Deteriorated battery
signal (WB)
(Between pins 9 and 5)
Backup power supply
stop signal (BS)
(Between pins 3 and 5)
Remote ON/OFF signal
(Between pins 6 and 7)
Beep
Signal input/output test start
Signal output test
Contact signal is forced to turn ON.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
60
BU
RE/BU
Signal input/output test end
Signal input test
While the signal is being
input, the status indicator
blinks and the beep sounds.
While the signal is being input, these status
indications blink and the beep sounds.
100
RE
4
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powli bu100re

Table of Contents