1-1-7
Communications Parameter Setup
Before you carry out communications with the E5@C, set up the communications unit number, baud
rate, and other parameters by carrying out the following procedure. For details on operations other than
communications parameter setup, refer to the E5
(Cat. No. H174) for the devices being used.
(1) Press the O Key for at least three seconds to move from the "operation level" to the
"initial setting level."
(2) Press the O Key for less than one second to move from the "initial setting level" to
the "communications setting level."
(3) Select the parameters as shown below by pressing the M Key.
(4) Use the D or U Keys to change the parameter set values.
psel
u-no
bps
len
sbit
prty
sdwt
*
Displayed only when the Protocol Setting parameter is set to CompoWay/F.
E5@C Digital Temperature Controllers Communications Manual (H175)
Protocol Setting
cwf
M
Communications Unit
No.
1
M
Communications
Baud Rate
9.6
M
Communications Data
Length *
7
M
Communications Stop
Bits *
2
M
Communications
Parity
even
M
Send Data Wait Time
20
M
1 Communications Methods
@
C Digital Temperature Controllers User's Manual
1
1 - 9