10

Mounting the burner

10
Mounting the burner
This chapter explains the basic steps involved in fitting a burner
NOTICE: Risk of system damage from use of incorrect
burner.
▶ Only use burners that meet the technical
requirements of the oil/gas-fired boiler Logano
G515 ( Chapter 3, page 8).
▶ Close the burner door and seal with 4 machine screws (M16 × 140)
( Chapter 7.8.3, page 21, Fig. 32, [3 to 6]). Tighten the machine
screws evenly crosswise.
You can obtain undrilled or predrilled burner plates (hole
pattern depends on burner) as accessories from
Buderus.
If you have ordered an undrilled burner plate, you will have to machine
the plate on site:
▶ Drill or cut the burner plate ( Fig. 66, [1]) to match the required
burner tube diameter Ø 10 – 5/8 inches (270 mm).
▶ Drill burner attachment holes using the burner flange as a template.
▶ Screw burner plate onto the burner door (seal with GP sealant rope;
diameter Ø 25/64 inches (10 mm)).
▶ Screw the burner to the burner plate.
▶ Cut out insulating rings to match the burner tube diameter
( Fig. 66, [2]).
▶ Fill the remaining gap between the burner door thermal insulation
and the burner tube  Fig. 66, [4]) using the appropriate insulating
rings ( Fig. 66, [3]).
▶ Connect the vent connection to the burner to ensure the inspection
window remains free of deposits.
1
Fig. 66 Mounting the burner
34
2
3
4
6 720 642 623-63.1o
Logano G515 – 6 720 647 208 (2014/09)