Operation
P08
Frequency reference lower limit
Setting range 0.1 to 120 (Hz)
3-6-5 Selecting the Processing after Recovery from a
Momentary Interruption
• Use this parameter to select the processing to be performed when a momentary power interruption
occurs.
• When setting 1 or 2 is selected, an alarm is output when low voltage is detected in the main circuit,
and the alarm is automatically cancelled when the normal voltage resumes.
• If the power interruption is longer that the time for which Inverter operation can be performed, the
operation after recovery from the power interruption will be the same as the startup operation.
P09
Momentary power interruption restart selection
Setting range 0 to 2
Set value
0 (0)
Inverter stops operating. (If the interruption lasts for 15 ms or longer, main circuit low voltage
will be detected and an error will occur.)
1 (1)
Inverter continues operating if power interruption is 0.5 s or less. (If a power interruption
occurs when 1 is set for 0.5 s, the main circuit low voltage is detected and outputs are
stopped while waiting for power to be restored. If power is restored within 0.5 s, operation
resumes.)
Inverter always continues operating. (If a power interruption occurs when 2 is set, outputs are
2 (2)
stopped while waiting for power to be restored. When power is restored, outputs are
resumed.)
3-6-6 Selecting Operation Commands
• This parameter selects the input method for specifying Inverter starting, stopping, and direction of
rotation.
• There are two methods that can be selected for operation commands. Select the best method for
the application.
P10
Operation command selection
Selected item Key/PLC
Selected item
Key (key)
Operation commands are performed using the Digital Operator keys.
PLC (plc)
Operation commands are performed using the STF and STR control inputs.
3-20
Setting unit 0.1 Hz (See note.) Default setting
Description
Description
Chapter 3
Changes during
No
operation
0.0
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
Key