Design
2-2-5 Connecting to a Digital Controller or Temperature
Controller
The 3G3JE provides an interface for connecting to the time-shared proportional pulse output of a
digital controller or temperature controller, so frequency references can be used when these devices
are used.
This section describes how to connect the Inverter to a digital controller.
Note The frequency references for time-shared proportional pulse output and frequency reference
selections cannot be used at the same time. If P11 (Frequency reference selection) is set to
T.C (Temperature controller time-shared proportional pulses), multi-step speed reference 0
(SS0) will be the temperature controller time-proportional pulse input and multi-step speed ref-
erence 1 (SS1) will be ignored.
Overview of Operation
The frequency setting is determined based on the ratio of ON time to OFF time within the frequency
reference upper and lower limit range.
• If the ON time is 0% and the OFF time is 100%, the frequency setting will be the frequency refer-
ence lower limit.
• If the ON time is 100% and the OFF time is 0%, the frequency setting will be the frequency refer-
ence upper limit.
For example, if time-shared proportional pulses are input when the frequency reference lower limit is
20 Hz, the upper limit is 60 Hz, the control period is 10 s, the ON time is 2 s, and the OFF time is 8 s,
then the frequency setting will be 28 Hz.
ON
OFF
2 s (ON time)
10 s (Control period of digital controller)
Frequency setting = Frequency reference lower limit + (Frequency reference upper limit − Frequency
reference lower limit) × (ON time/Control period)
= 20 Hz + (60 Hz − 20 Hz) × (2 s/10 s)
= 20 Hz + 40 Hz × 0.2
= 28 Hz
Time Required to Switch Frequency Reference
The frequency of the time-proportional pulse input is calculated based on the ratio between the ON
time and OFF time. At least one time-shared proportional pulse control cycle of the digital controller
or temperature controller is required to switch the 3G3JE's frequency reference.
Digital Controller and Temperature Controller Output Specifications
The digital controller or temperature controller that is connected must have the following output spec-
ifications.
• Relay output models
• Voltage output models (12 V ± 10% output or 24 V ± 10% output)
2-24
8 s (OFF time)