Operation
Setting Frequency References 1 to 4
sp1
Key sequence
None
1 s min.
1 s min.

3-5-2 Setting Acceleration and Deceleration Times

• The acceleration time and the deceleration time are set separately.
• The acceleration time is the time required to accelerate from 0% to 100% of the maximum output
frequency (P06), and the deceleration time is the time required to decelerate from 100% to 0% of
the maximum output frequency.
• The setting unit for the acceleration and deceleration times is 0.1 s for less than 100 s, and 1 s for
100 s or more.
• If the load inertia is high, the acceleration and deceleration times must be increased. For details,
refer to 7-1 Selecting the Inverter at the end of this manual.
• The acceleration/deceleration time between 0 and the frequency reference is calculated with the
following formula.
Acceleration/deceleration time = (Acceleration/deceleration time setting) × (Frequency reference)
÷ (Maximum output frequency setting)
Note When accelerating from a stopped condition, the starting DC breaking time must be added.
sp3
50
Indicator
Display example
@ Hz set
None
sp1
None
sp3
None
28.3
None
32.0
None
sp3
@ Hz set
None
The entire display and simplified-LED indicators
will light (except for the COM indicator) when
6.0
the power supply is turned ON. The present fre-
quency reference will be displayed on the data
display.
Pressing the Enter Key for 1 s or longer
changes the mode to the adjustment mode.
sp1 will be displayed on the data display.
Select the item to be displayed using the Incre-
ment and Decrement Keys.
When the Enter Key is pressed, the present set
value for the selected item will be displayed.
Set the frequency reference using the Incre-
ment and Decrement Keys. The data display
will flash.
When the Enter Key is pressed, the set value
will be entered. When the data display stops
flashing, operation will be returned to the set
item selection.
Press the Enter Key for at least 1 s to return to
the RUN mode.