Design
2-2-6 Harmonics Suppression in General-purpose Inverters
(Input Current of 20 A Maximum)
When equipped with the AC Reactor specified in section 5-2-5, the 3G3JE meets the harmonic sup-
pression guideline for general-purpose inverters (inverters with an input current of 20 A maximum)
issued by the Japan Electronic Device Industrial Council (JEDIC).
2-2-7 Guideline to Reduce Harmonics Emissions in Appliances
Receiving High Voltages or Special High Voltages
The 3G3JE meets the Guideline to Reduce Harmonics Emissions in Appliances Receiving High Volt-
ages or Special High Voltages (JEITA).
Guideline Applicability
This guideline is applicable to the following appliances.
1. Appliances receiving power from a 6.6-kV network with a total capacity exceeding 50 kVA consid-
ering the harmonics emission rate for each type of installed device emitting harmonics (called the
equivalent capacity)
2. Appliances receiving power from a 22-kV or 33-kV network with equivalent capacity exceeding
300 kVA
3. Appliances receiving power from a 66-kV or higher network with equivalent capacity exceeding
2,000 kVA
The limit for harmonic current, calculation methods for the equivalent capacity, and calculation meth-
ods for the harmonic current for appliances receiving 6.6 kV are described below.
Limit of Harmonic Current
The allowable value for the harmonic current flowing to the network from special appliances is cal-
culated for each harmonic number by multiplying the harmonic current limit per kilowatt of con-
tracted power given in the following table by the contracted power (in kilowatts).
Limits to Harmonic Current per kW of Contracted Power
Received
5th
voltage (kV)
6.6
3.5
2-34
7th
11th
13th
2.5
1.6
1.3
17th
19th
23rd
1.0
0.90
0.76
Chapter 2
(Unit: mA/kW)
Higher
than 23rd
0.70