2.3.2 Control circuit terminals

The control circuit terminal board is common to all equipment.
⇒ How to set input terminal function, refer to section 7.
Terminal
Input/
symbol
output
Shorting across F-CC causes forward
F
Input
rotation; open causes deceleration stop.
(Across ST-CC is short state.)
Shorting across R-CC causes reverse
R
Input
rotation; open causes deceleration stop.
(Across ST-CC is short state.)
The motor is on standby if ST and CC are
connected. It coasts to a stop if this
ST
Input
connection is broken. This terminal can be
used for interlocking.
Shorting and then opening RES-CC
cancels the status held by an inverter
RES
Input
protective function. When the inverter is
operating normally, shorting and then
opening RES-CC produces no effect.
Shorting across S1-CC causes preset
S1
Input
speed operation.
Shorting across S2-CC causes preset
S2
Input
speed operation.
Shorting across S3-CC causes preset
S3
Input
speed operation.
SW3: When SW3 is in the S4 position, S4
RR/S4
Input
and CC are shorted and preset speed
operation is selected.
24Vdc power output (when SW1 is in any
Output
position other than PLC)
24V internal output terminal
P24/
PLC
If SW1 is turned to the PLC position, this
Input
terminal can be used as a common terminal
when an external power supply is used.
Common
Digital signal equipotential (0V) terminal for the
CC *1
to input/
control circuit and equipotential (0V) terminal
output
for an optional control power supply backup.
Shorting bar between ST-CC (VFAS1- * * * * *
Function
Voltage free contact
input
B-9
Electrical
Inverter internal circuits
specifications
SW1=SINK (INT): Sink logic (When the
• @ • @ • @ • @
internal 24V power supply is used)
24Vdc-5mA or less
Lan current signal.
P24/PLC
Choose low current
contacts to avoid
SINK
poor attaching.
*Sink/source selectable
2.2kƒ ¶
with SW1
CC
Sink input
ON: Less than DC10V
OFF:DC16V or more
Source input
SW1=SINK (PLC): Sink logic (When an
external 24V power supply is used)
ON:DC11V or more
OFF: Less than DC5V
P24/PLC
Note:
SINK
Even when an
external power supply
is used (in sink logic
2.2kƒ ¶
mode, i.e., when SINK
CC
(PLC) is selected),
connect the reference
potential-side (0V
SW1=SOURCE (INT/PLC):
side) cable from the
Source logic (When the internal 24V
power supply to the
power supply or an external 24V power
supply is used)
CC terminal.
24Vdc-200mA
2.2kƒ ¶
SINK
-
SW1
P24/PLC
CC
-
E6581301
-WN)
If SW1 is set to 1
SW1
SOURCE
P24
2.2kƒ ¶
If SW1 is set to 2
SW1
SOURCE
P24
2.2kƒ ¶
If SW1 is set to 3
2.2kƒ ¶
P24
SOURCE
2