6.17 Adjustment parameters

6.17.1 Pulse train output for meters
 : Logic output/pulse train output selection (OUT-NO)
 : Pulse train output function selection (OUT-NO)
 : Maximum nembers of pulse train
• Function
Pulse trains can be sent out through the OUT-NO output terminals.
To do so, it is necessary to select a pulse output mode and specify the number of pulses.
Ex.: When operations frequencies (0 to 60Hz) are put out by means of 0 to 600 pulses
 =60.0,  =1,  =0,  =0.60
Title
Logic output/pulse train

output selection (OUT-NO)
Pulse train output function

selection (OUT-NO)
Maximum numbers of

pulse train
Digital panel meter for reference
Type: K3MA-F (OMRON)
Connection terminal: OUT-E4, NO-E5
Note 1: When item of f676 reachs "Reference of max. value", the number of pulse train set by f677 are
sent to output terminals (OUT-NO)
Note 2: The pulse ON/OFF duty ratio is fixed at 50%.
Note 3: The minimum pulse output rate is 25 pps. Keep in mind that no pulses can be put out at any rate
smaller than 25 pps.
Note 4:  =  is the motor drive frequency.
Function
0: Logic output
1: Pulse train output
0: Output frequency
1: Output current
2: Set frequency
3: Input voltage (DC detection)
4: Output voltage command value
5-11: -
12: Frequency setting value (after
correction)
13: VI input value
14: -
15: Fixed output 1
(Output current: 100% equivalent)
16: Fixed output 2
(Output current: 50% equivalent)
17: Fixed output 3
(Other than the output current: 100%
equivalent)
18: Communication data
19-22: -
0.50-1.60 (kpps)
F-55
Adjustment range
E6581595
Reference
Default
of maximum
value of
setting

0
6

185%

150%
150%
-

10 V/20 mA
-
0
185%
185%
100%
100.0%
-
0.8