CX-Process Monitor
Item
Online
User Con-
operation
figuration
functions
screen
Online
System
operation
Fixed
functions
screen
16
Graphic
This screen displays changes in the plant status using graphic elements
screen
representing plant devices pasted to the screen from the graphic elements
library (provided with the CX-Process Monitor). The maximum number of
screens is 200.
Fixed graphic elements provided in library: Devices, thermometers,
transmitters, orifices, text
Variable graphic elements provided in library:
Analog input: Bar graph display, numeric indication, tanks
Analog output: Numeric setting (by AO Terminal Settings from Computer
block)
Contact input: Pumps, valves, indicators
Contact output: Switches (by DO Terminal Settings from Computer block)
Annunciator
This screen notifies the operator of alarms or errors that occur by changing
screen
the display color and emitting sound. At the same time, a 32-character
message is displayed over two lines on screen elements.
A total of 16 screen elements (4 columns x 4 lines) can be displayed on each
screen. The maximum number of screens is 5.
Operation
This screen displays pre-registered 128-character messages over two lines
Guide
together with the date of occurrence when the specified internal switch is set
Message
to ON.
screen
Max. number of registerable messages: 100, Number of display colors: 7
Up to 1000 messages are displayed in a single screen.
Output possible in CSV format.
Alarm Log
A record of alarms (time of error occurrence, tag name, PV or MV current
screen
value at occurrence, alarm type, etc.) that occur and that are input from the
Control and Alarm blocks is saved and displayed as a list later.
Up to 1000 alarm messages are displayed in a single screen.
Output possible in CSV format.
Operation
A record of changes (date and time of change, tag name, original ITEM data
Log screen
setting, new ITEM data setting, etc.) made to ITEM data on the Loop Control
Unit in the Control or Tuning screen is saved and displayed as a list later.
Up to 1000 operation messages are displayed in a single screen.
Output possible in CSV format.
System
This screen displays the Loop Control Unit operation run/stop commands,
Monitor
operation start/stop status, execution errors, RAM sum errors, battery errors,
screen
and the status of the Controller Link Data Link.
System
This screen displays a log of the run/stop history and a history of execution
Monitor Log
errors that occur on the Loop Control Unit together with the date of
screen
occurrence.
Output possible in CSV format.