Setup Using The Dtm - Omron GRT1 - 27-11-2006 Operation Manual

Profibus communication unit
Table of Contents

Advertisement

Setup the GRT1-PRT Configuration
3-3-2

Setup Using the DTM

Parameter Area Tab
PROFIBUS Settings Box
Station Address Setting
!Caution It is recommended not to use address 00, since in that case the messaging
Watchdog Control Setting
GRT1-PRT DTM window which pops up after double-clicking the GRT1-PRT
entry in the Network View is shown below.
Note The buttons on the bottom will be enabled only when the DTM is on-line.
The Parameter Area Tab, shown above, defines the parameter settings for the
GRT1-PRT. In this Tab are two distinct sub areas of parameters.
• PROFIBUS Settings Box
• Extensions Box
The PROFIBUS Settings Box contains
• the Station address,
• the Watchdog Control settings,
• the Group Selection
• the FINS Fragment length.
The Station Address is automatically assigned by the Master DTM. Only
change this setting if the physical device has a different address from the one
assigned by the Master DTM. The allowable range is 00 to 99.
services will not work. Address 00 is reserved for Master Units.
The Watchdog Control check box allows Enable/Disable of the Communica-
tion watchdog. If the Watchdog has been enabled, the GRT1-PRT will revert
to a safe state, in case the PROFIBUS communication stops. The Watchdog
will be Enabled by default, and it is recommended to leave it Enabled.
Note The Watchdog timeout Interval is defined by the PROFIBUS Master DTM and
depends on the Bus parameters as well as on the total amount of Slave
devices on the network.
Section 3-3
43