Unit Components
Indicator
BF
PROFIBUS Failure
TS
SmartSlice I/O System
communication status
UNIT PWR
I/O PWR
2-1-3

Switch Settings

Rotary Switches
5
5
0
0
x10
x10
x1
x1
1,2,3...
Note
Colour
Status
Red
Not lit
No PROFIBUS communication errors occurred. I/O Data Exchange is
in progress.
Flashing The parameter settings sent by the PROFIBUS Master unit are invalid.
No I/O Data Exchange is possible.
Lit
No PROFIBUS communication has been detected by the Unit.
--
Not Lit
• Power not being supplied.
• Communication has not started with SmartSlice I/O Unit.
• Over current detected.
Green
Flashing SmartSlice I/O Unit added to the system (Flashing once every 1 s)
Backup/Restore function operating (Flashing once every 0.5 s)
• Restoring settings to SmartSlice I/O Unit, backup function operating.
• Downloading SmartSlice I/O Unit settings.
Lit
Communication with SmartSlice I/O Unit established.
Red
Flashing Non-fatal communication error occurred.
• Communication timeout
• Verification error occurred with registered table.
• Different model Unit detected after I/O Unit replacement.
Lit
Fatal communication error occurred.
Failure occurred while restoring settings to I/O Unit or downloading I/O
Unit settings (Lit for 2 s)
Green
Not Lit
Power supply to the Unit is not present (All other LED indicators are
also OFF).
Lit
Power supply to the Unit is present.
Green
Not Lit
Power supply to the SmartSlice I/O is not present. The SmartSlice I/O
Units may be operative, but no output is available.
Lit
Power supply to the SmartSlice I/O is present.
Two rotary switches on the front of the GRT1-PRT, marked x10 and x1, are
provided to set the PROFIBUS device address of the Unit. The address can
be set in the range of 00 through 99 (decimal). The device address on the Unit
must be the same as the address used in the master's configuration. The
device address is used to uniquely identify PROFIBUS Communication Unit
on the PROFIBUS DP network. Selecting a non-unique address for the unit
will prevent the unit from communicating properly with the Master unit.
In order to set the device address, perform the following steps.
1. Turn OFF the power supply before setting the device address.
2. Set the switch to the (new) device address. Use a small screwdriver to
make the setting, taking care not to damage the rotary switch. The station
address is factory-set to 0.
3. Turn ON the power again.
1. Always turn OFF the power to the Unit before changing the device address
setting. The Unit only reads the address setting during the initialization fol-
lowing a power-up, i.e. any changes after power up will have no effect.
2. The PROFIBUS Communication Unit detects the Master's communication
baud rate automatically. Setting the baud rate is not required.
Section 2-1
Meaning
13