Wiring the GRT1-PRT
Wiring Example
PROFIBUS
Communication Unit
CPU
Connector
Power supply
(24 VDC)
GRT1-TBL Turnback Unit (Left)
2-3-2

Wiring Methods

Supplying Power to
the Units
GRT1-PD2 I/O Power Supply Unit
I/O
I/O
(IN)
(IN)
I/O
I/O
power
power
supply
supply
I/O
I/O
I/O
(AD)
(AD)
(AD)
I/O
power
supply
Connect the power supply wires (24 VDC) to the PROFIBUS Communication
Unit's screwless clamping power supply terminals. If pin terminals are used
on the wire ends, the pin terminals can just be inserted to wire the power.
These terminals supply power to both
the PROFIBUS Communication Unit's
internal circuits and the connected
SmartSlice I/O Units' internal circuits.
Note
The GRT1-TBL Left Turnback Unit has the same screwless clamping power
supply terminals as the PROFIBUS Communication Unit. These terminals are
wired in the same way, by inserting the power supply wires.
GRT1-TBR Turnback Unit (Right)
I/O
I/O
I/O
I/O
I/O
(OUT)
(OUT)
(OUT)
(OUT)
(OUT)
I/O
I/O
End Unit
(AD)
(AD)
Holes for wires
(pin terminals)
Connector
Do not exceed 80 W
power consumption
in one block.
Power is not supplied through
the Turnback Cable.
Do not exceed 80 W
power consumption
in one block.
Release button
Press the release button with
a screwdriver and pull out the
wire (pin terminal).
24 VDC
Section 2-3
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Profibus - 27-11-2006Smartslice grt1-seriesGrt1-prt