YPP6830 Explosion-Proof Pulse Input Rate/Totalizer
Total Overflow
The total can display up to
9,999,999,999,999. Up to 9,999,999
And Rollover
can be displayed on the lower display
normally. An overflow display will
toggle between the first six digits and
last seven digits (999999 <> 9999999)
for a 13-digit total. The total will rollover
beyond thirteen digits. The T indicator
on the display will flash to indicate total
overflow, and the six most significant
digits (first six numbers of the total) are
indicated with the flashing overflow
symbol .
Grand Total
The grand total can display up to
9,999,999,999,999. Up to 9,999,999
Overflow And
can be displayed on the lower display
Rollover
normally. An overflow display will
toggle between the first six digits and
last seven digits (999999 <> 9999999)
for a 13-digit total. The grand total will
rollover beyond thirteen digits. The GT
indicator on the display will flash to
indicate grand total overflow, and the
six most significant digits (first six
numbers of the grand total) are
indicated with the flashing overflow
symbol .
External Total
External total reset connections are
Reset
made between RST and COM.
Logic High: 1.4 V, 3.3V max;
Logic Low: < 0.8 V.
32 ms debounce.

4-20 mA Transmitter Output

Output Source
Rate/process, total, grand total, or
disabled
Scaling Range
4.000 to 20.000 mA for any display
range.
Disable
If disabled, the output will output 3.2
mA
Calibration
Factory Calibrated:
0.0 to 1000.0 = 4- 20 mA output
Underrange
Output Underrange: 3.8 mA
Overrange
Display Overrange: 20.5 mA
Output Overrange: 20.5 mA
Accuracy
± 0.05% of calibrated span ± 0.004 mA
Temperature Drift 0.08 µA/C max from -40 to 75C
ambient
External Loop
30 VDC maximum
Power Supply
Output Loop
Power
Resistance
Supply
24 VDC
30 VDC
Note: loop-powered backlight subtracts
150
from maximum resistance
figures above.
Minimum
Maximum
10 
750 
100 
1100 
8

Open Collector Output

Output
Two open collector pulse outputs Out 1
Assignment
and Out 2.
Individually programmable for rate,
total, or grand total alarms; rate, total,
or grand total pulse outputs; or
retransmitting of pulse inputs; constant
timed pulse output; quadrature outputs
(requires Out 1 and Out 2); or off.
Rating
Isolated open collector, sinking NPN
30 VDC @ 150 mA max.
Alarm Output
Assign to rate for high or low alarm trip
point.
Assign to total or grand total for total or
grand total alarms.
Alarm Deadband 0-100% FS, user selectable
Alarm
Front panel ENTER button resets
Acknowledge
output and screen indication.
Pulse Output
The InvK-Factor (couNT) is
(Count)
programmable from 0.000001 to
9999999. Total and grand total pulses
InvK-Factor =
are generated for every total or grand
Volume/Pulse
total increment selected. (e.g. InvK-
Factor = 100 gal/p will generate one
pulse every time the total is
incremented by 100 gallons).
Rate pulses are generated as a scaled
output of the input frequency with one
output pulse per InvK-Factor (count).
Rate retransmission outputs one pulse
per one input pulse, up to the
maximum output speed.
Pulse Output
Unless otherwise stated, pulses are
Pulse Width
50% duty cycle for required frequency.
A pulse rate retransmit output will
generate 100 to 130 μs pulses at the
falling edge of every input pulse.
Pulse Output
5 kHz, pulse width at 50% duty cycle. If
Maximum
the programming of the outputs would
Frequency
exceed 5 kHz, the meter will display
pUlse OVERRNG
Quadrature
Output set to quadrature will lag the
Output
other pulse output by 90°
(1/4 duty cycle) at output frequency.
Minimum 1 Hz
Timer Output
Programmable On and Off time,
repeating cycle. Minimum On time:
0.01 second, maximum On time:
10,000 seconds. Minimum Off time
(Delay Period): 0.1 second, maximum
Off time (Delay Period): 100,000
seconds. Ýelay Period: Countdown
time delay (Off) after start is pressed.
Ðn Time: Time the open collector stays
on.

Serial Communications

Protocol
Modbus® RTU
Meter Address/
1 - 247
Slave Id
Baud Rate
1,200; 4,800; 9,600; 19,200; 38,400;
57,600; or 115,200 bps
Transmit Time
Programmable between 0 and 199 ms
Delay
Parity/Stop Bit
Even, odd, none with 1 stop bit, or
none with 2 stop bits
Max of 1.5 character times or 750 μs
Byte-To-Byte
Timeout
Note: Refer to Modbus Register Tables at www.yokogawa.com/us for
details.