Mitsubishi MELSEC F FX-40DU-E Handy Manual page 38

Table of Contents

Advertisement

4.
USER SCREEN MODE
Guide to Screen
0
(3) NUMBER
These objects display the data of programmable controller word devices (T and C current values
and settings,
D,
V and
2).
Applicable devices
T, C (current value and setting), D (16-bit), D (32-bit), V,
2.
Display format
Decimal: Left to right.
Maximum number of displayed digits:
12 digits (the minus sign and decimal point are each counted as one digit).
High speed counter
C235 (32-bit)
Example
-21 47483648
21 47483647
to
~
11 digits
10 digits
It is possible to set a maximum value and minimum value for the current value of displayed
devices. If the data exceeds the maximum number of digits that can be displayed, question
marks "?" will be displayed.
Example
Specified programmable controller device : DO
Number of digits: 4
MAX.:
2000
MIN.:
0
Size
w
One-byte, two-byte, vertical x l to x4 magnification, horizontal x l to x4 magnification.
The vertical and horizontal magnifications can be set independently in the range x l to x4 but
note that it will not be possible to display data with a large number of digits if that data will not
fit in the display area.
Number of displayed objects
.
16-bit devices are counted as one object and 32-bit objects are counted as two objects,
regardless of the number of digits.
The maximum number of displayed number objects is 10 per screen, but note that if there are
any bar graph objects (described on the next page), they will be counted in the same total.

Advertisement