Application guidelines
6.6 Setting up the power consumption control
Installer reference guide
60
Setup
▪
Connect power meter 1 to X5M/5 and X5M/6.
▪
Connect power meter 2 to X5M/3 and X5M/4.
See
"9.3.4 To connect the electricity
Power meter types
▪
Power meter 1: Single- or three-phase power meter according to the power
supply of the outdoor unit.
▪
Power meter 2:
-
In case of a single-phase backup heater configuration, use a single-phase
power meter.
-
In other cases, use a three-phase power meter.
Example
Single-phase outdoor unit with a three-phase backup heater:
0
0
58 0
1 5 0
a
c
X5M/5+6
S1S
e
e
X5M/9+10
g
h
A
B
A Outdoor unit
B Indoor unit
C DHW tank
a Electrical cabinet (L
b Electrical cabinet (L
c Power meter (L
d Power meter (L
e Fuse (L
/N)
1
f Fuse (L
/L
/L
1
2
g Outdoor unit (L
h Indoor unit (L
i Backup heater (L
j Booster heater (L
S1S Preferential kWh rate power supply contact
You can use the following power consumption controls. For more information
about the corresponding settings, see
#
1
"6.6.1 Permanent power
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) with one permanent
setting.
▪
Limitation of power in kW or current in A.
4
meters" [
0
0
58 0
1 5 0
b
d
45 08 96
.0 05
X5M/3+4
f
e
i
j
C
/N): Preferential kWh rate power supply
1
/L
/L
/N): Normal kWh rate power supply
1
2
3
/N)
1
/L
/L
/N)
1
2
3
/N)
3
/N)
1
/N)
1
/L
/L
/N)
1
2
3
/N)
1
"Power consumption
Power consumption control
4
limitation" [
61]
123].
4
control" [
EPRA14~18D + ETBH/X16E
Daikin Altherma 3 H HT W
4P644736-1D – 2023.10
214].