Daikin ETBH16E9W Installer's Reference Manual page 222

Table of Contents

Advertisement

10
|
Configuration
Alarm output
Auto restart
Power saving function
Installer reference guide
222
Alarm output
#
Code
[9.D]
[C–09]
Alarm output logic
[C-09]
0
Closed output
1
Open output
Auto restart
When power returns after a power supply failure, the auto restart function
reapplies the user interface settings at the time of the power failure. Therefore, it
is recommended to always enable the function.
If the preferential kWh rate power supply is of the type that power supply is
interrupted, always enable the auto restart function. Continuous indoor unit
control can be guaranteed independent of the preferential kWh rate power supply
status, by connecting the indoor unit to a separate normal kWh rate power supply.
#
Code
[9.E]
[3-00]
Power saving function
NOTICE
Power saving function. The power saving function is only applicable for V3 models. If
you want to use the power saving function, on the outdoor unit PCB make sure to
connect X804A to X806A. For more information, see
Alarm output: Indicates the logic of alarm
output on digital I/O PCB during high level indoor
unit error malfunctioning. Low level errors
(caution/warning) will NOT be transmitted to
alarm output.
0 Abnormal: The alarm output will be
powered when an alarm occurs. By setting this
value, a distinction is made between the
detection of an alarm, and the detection of a
power failure.
1 Normal: The alarm output will NOT be
powered when an alarm occurs.
See also table below (Alarm output logic).
Alarm
No alarm
Open output
Closed output
Auto restart:
0: Manual
1: Automatic
Description
No power supply
to unit
Open output
Description
4
"In case of V3
models" [
EPRA14~18D + ETBH/X16E
Daikin Altherma 3 H HT W
4P644736-1D – 2023.10
 107].