Code
[5.6]
[6-0D]
See the operation manual for more details.
INFORMATION
Risk of space heating capacity shortage for domestic hot water tank without internal
booster heater: In case of frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when selecting the following:
Tank > Heat up mode > Reheat only.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
#
Code
[5.7.1]
[2‑01]
[5.7.2]
[2‑00]
[5.7.3]
[2‑02]
[5.7.4]
[2‑03]
[5.7.5]
[2‑04]
Description
Heat up mode:
0: Reheat
only: Only reheat operation is
allowed.
1: Schedule + reheat: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
2: Schedule only: The domestic hot water
tank can ONLY be heated according to a
schedule.
Description
Activation:
0: No
1: Yes
Operation day:
0: Every day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
Start time
Tank setpoint:
55°C~75°C
Duration:
5~60 minutes
EPRA14~18D + ETBH/X16E
Daikin Altherma 3 H HT W
4P644736-1D – 2023.10