4P644736-1D – 2023.10
Setpoint mode
#
Code
[5.B]
N/A
WD curve
When weather-dependent operation is active the desired tank temperature is
determined automatically depending on the averaged outdoor temperature: low
outdoor temperatures will result in higher desired tank temperatures as the cold
water tap is colder and vice versa.
In case of Schedule
preparation, the storage comfort temperature is weather-dependent (according to
the weather-dependent curve), the storage economic and reheat temperature are
NOT weather-dependent.
In case of Reheat
temperature is weather-dependent (according to the weather-dependent curve).
During weather-dependent operation, the end-user cannot adjust the desired tank
temperature on the user interface. Also see
4
curve" [
 151].
#
Code
[5.C]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
Margin
In domestic hot water operation, the following hysteresis value can be set for the
heat pump operation:
Setpoint mode:
Fixed
Weather dependent
only or Schedule
only domestic hot water preparation, the desired tank
WD curve:
T
DHW
[0-0C]
[0-0B]
[0-0E]
T
: The desired tank temperature.
DHW
T
:
The
a
temperature
[0-0E]: low outdoor ambient temperature: –
40°C~5°C
[0-0D]: high outdoor ambient temperature:
10°C~25°C
[0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature:
-
45°C~[6‑0E]°C (for E models)
-
min(45, [6‑0E])°C~[6‑0E]°C (for E7 models)
[0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C
10
Configuration
|
Description
+
reheat domestic hot water
"10.4  Weather-dependent
Description
T
a
[0-0D]
(averaged)
outdoor
Installer reference guide
ambient