Miller Maxstar 400 Owner's Manual page 42

Hide thumbs Also See for Maxstar 400:
Table of Contents

Advertisement

D. Maxstar 800 Models
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
CE-marked equipment shall only be used on a supply network that is a three-phase, four-wire system with an earthed neutral.
.
Actual input voltage should not be 10% less than minimum (5% for 380 volt CE models) and/or 10% more than maximum input voltages listed
in table. If actual input voltage is outside this range, output may not be be available.
NOTICE − INCORRECT INPUT POWER can damage this welding power source. Phase to ground voltage shall not exceed +10% of rated input
voltage.
Input Voltage (V)
Rated Maximum Supply Current I
Maximum Effective Supply Current I
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG (mm
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG (mm
Reference: 2017 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16) and is based on allowable ampacities of insulated copper conductors having a temperature rating of 167°F (75°C) with not more than
three single current−carrying conductors in a raceway. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table
400.5(A) for flexible cord and cable requirements.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
Input Voltage (V)
Rated Maximum Supply Current I
Maximum Effective Supply Current I
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG (mm
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG (mm
Reference: 2017 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16) and is based on allowable ampacities of insulated copper conductors having a temperature rating of 167°F (75°C) with not more than
three single current−carrying conductors in a raceway. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table
400.5(A) for flexible cord and cable requirements.
.
A complete Parts List is available at www.MillerWelds.com
(A)
1max
(A)
1eff
1
2
Time-Delay Fuses
3
Normal Operating Fuses
2
4
)
2) 4
(A)
1max
(A)
1eff
1
2
Time-Delay Fuses
3
Normal Operating Fuses
4
2
)
2) 4
Three-Phase
208
230
380
120
109
65
70
62
37
150
125
80
175
150
90
4 (21.1)
6 (13.3)
8 (8.3)
96 (29)
75 (23)
132 (40)
6 (13.3)
6 (13.3)
8 (8.3)
Single-Phase
208
230
400
126
112
61
97
87
48
150
125
70
175
150
90
3 (26.6)
3 (26.6)
8 (8.3)
98 (30)
122 (37)
130 (40)
6 (13.3)
6 (13.3)
8 (8.3)
400
460
575
61
53
42
35
30
24
70
60
50
90
70
60
8 (8.3)
10 (5.2)
10 (5.2)
148 (45)
129 (39)
203 (62)
8 (8.3)
10 (5.2)
10 (5.2)
460
575
53
41
41
32
60
50
70
60
8 (8.3)
8 (8.3)
172 (52)
275 (84)
8 (8.3)
10 (5.2)
OM-275857 Page 33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dynasty 800Dynasty 400Maxstar 800