B. Maxstar 400 Models
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
CE-marked equipment shall only be used on a supply network that is a three-phase, four-wire system with an earthed neutral.
.
Actual input voltage should not be 10% less than minimum (5% for 380 volt CE models) and/or 10% more than maximum input voltages listed
in table. If actual input voltage is outside this range, output may not be be available.
NOTICE − INCORRECT INPUT POWER can damage this welding power source. Phase to ground voltage shall not exceed +10% of rated input
voltage.
Input Voltage (V)
Rated Maximum Supply Current I
Maximum Effective Supply Current I
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG (mm
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG (mm
Reference: 2017 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16) and is based on allowable ampacities of insulated copper conductors having a temperature rating of 167°F (75°C) with not more than
three single current−carrying conductors in a raceway. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table
400.5(A) for flexible cord and cable requirements.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
Input Voltage (V)
Rated Maximum Supply Current I
Maximum Effective Supply Current I
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG (mm
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG (mm
Reference: 2017 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16) and is based on allowable ampacities of insulated copper conductors having a temperature rating of 167°F (75°C) with not more than
three single current−carrying conductors in a raceway. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table
400.5(A) for flexible cord and cable requirements.
.
A complete Parts List is available at www.MillerWelds.com
(A)
1max
(A)
1eff
1
2
Time-Delay Fuses
3
Normal Operating Fuses
2
4
)
2) 4
(A)
1max
(A)
1eff
1
2
Time-Delay Fuses
3
Normal Operating Fuses
4
2
)
2) 4
Three-Phase
208
230
380
50
45
27
26
23
14
60
50
30
80
70
40
10 (6)
10 (6)
14 (2.5)
62 (19)
76 (23)
81 (25)
10 (6)
10 (6)
14 (2.5)
Single-Phase
208
230
400
62
55
30
37
33
18
70
60
35
90
80
45
8 (10)
8 (10)
12 (4)
68 (21)
85 (26)
106 (32)
8 (10)
8 (10)
12 (4)
400
460
575
25
22
17
13
12
9
30
25
20
35
35
25
14 (2.5)
14 (2.5)
14 (2.5)
92 (28)
121 (37)
196 (60)
14 (2.5)
14 (2.5)
14 (2.5)
460
575
26
20
18
12
30
25
40
30
12 (4)
14 (2.5)
139 (42)
145 (44)
12 (4)
14 (2.5)
OM-275857 Page 31