3.
4.
5.
NOTE:
Figure 10-11 Power Deviation Dialog Box
Table 10-8
Power Deviation Enable
Sample Period
Stabilization Time
Deviation Limit Field
Power Deviation
The Setup Alarm dialog window shows. Refer to
Touch each field to enter the changes and then touch the Accept button.
Refer to
Table 10-8
for the field descriptions.
To enable the feature, touch the Power Deviation Enable check box so a check mark
shows.
To accept changes, touch the Exit button.
Before the Power Deviation routine can be executed, at least one zone in the system
must be classified based on similar function and operation.
Power Deviation Settings
Setting
v 1.0 — February 2020
Used to enable or disable the feature.
The interval of time the system uses to calculate a baseline
average power value (that is, to "know" the mold). The
default value is 2 minutes and the range is from 1-10
minutes.
The interval of time the system will take after all active zones
have reached their setpoints before it starts the Sample
Period. The default value is 2 minutes and the range is from
1-10 minutes.
This field is used by the system to decide the tolerance value
that is used to communicate an error. This value will only be
used if the value calculated by the system cannot be used.
The default value is 10% and the range is from 1-100%,
specified in 1% increments.
Figure
10-11.
Description
System Setup Screen
127