" " DC dynamic brake (Pr. 10, Pr. 11, Pr. 12)

4.2.7 DC injection brake (Pr. 10 to Pr. 12)

Pr. 10 "DC injection brake operation frequency"
Pr. 11 "DC injection brake operation time"
Pr. 12 "DC injection brake voltage"
By setting the DC injection brake voltage (torque),
operation time and operation starting frequency, the stopping accuracy of positioning
operation, etc. or the timing of operating the DC injection brake to stop the motor can
be adjusted according to the load.
Parameter
Factory
Number
Setting
10
11
12
<Setting>
! Use Pr. 10 to set the frequency at which the DC injection brake operation is started.
! Use Pr. 11 to set the period during when the brake is operated.
! Use Pr. 12 to set the percentage of the power supply voltage.
! The setting value for Pr. 12 when using the inverter-dedicated motor (constant-
torque motor).
FR-E520-0.1KND to 7.5KND ............................................................ 4% (Note)
Note: When the Pr. 12 value is as factory-set, changing the Pr. 71 value to the
setting for use of a constant-torque motor changes the Pr. 12 value to 4%
automatically.
Install a mechanical brake. No holding torque is provided.
Setting
Range
3Hz
0 to 120Hz
0.5 s
0 to 10 s
6%
0 to 30%
CAUTION
Get other manuals https://www.bkmanuals.com
Pr.12
DC injection
Operation
brake voltage
voltage
69
PARAMETERS
Operation
Pr.10
frequency
Time
Time
Pr.11
Operation time