" Starting frequency (Pr. 13)

4.2.8 Starting frequency (Pr. 13)
Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
! Set the starting frequency at which the start signal is switched on.
Parameter
Factory
Number
Setting
13
0.5Hz
Note: The inverter will not start if the frequency setting signal is less than the value
set in Pr. 13 "starting frequency".
For example, when 5Hz is set in Pr. 13, the motor will not start running until
the frequency setting signal reaches 5Hz.
When the Pr. 13 setting is equal to or less than the Pr. 2 value, note that
merely switching on the start signal will start the motor at the preset
frequency if the command frequency is not input.
Setting
Output frequency
Range
0 to 60Hz
CAUTION
70
Get other manuals https://www.bkmanuals.com
PARAMETERS
Related parameters
Pr. 2 "minimum frequency"
(Hz)
60
Pr.13
0
Frequency setting signal(V)
Foward rotation
ON