Reset Selection/Disconnected Pu Detection/Pu Stop Selection (Pr. 75) - Mitsubishi FR-E500 Series Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-E500 Series:
Table of Contents

Advertisement

" " Voltage input (Pr. 73)

" Reset selection/disconnected PU detection/PU stop selection (Pr. 75)

4.2.23 Reset selection/disconnected PU detection/PU stop
selection (Pr. 75)
Pr. 75 "reset selection/disconnected PU detection/PU stop selection"
You can select the reset selection, disconnected PU (FR-PU04) detection function and
PU stop selection function.
! Reset selection
! PU disconnection detection : When it is detected that the PU (FR-PU04) is
! PU stop selection
Parameter
Factory
Number
Setting
75
<Setting>
Pr. 75
Reset Selection
Setting
Reset input normally enabled.
0
Reset input enabled only when the
1
protective function is activated.
Reset input normally enabled.
2
Reset input enabled only when the
3
protective function is activated.
Reset input normally enabled.
14
Reset input enabled only when the
15
protective function is activated.
Reset input normally enabled.
16
Reset input enabled only when the
17
protective function is activated.
: You can select the reset function input timing.
disconnected from the inverter for more than 1 second,
the inverter outputs an alarm code (E.PUE) and comes
to an alarm stop.
: When an alarm occurs in any operation mode, you can
stop the inverter from the PU by pressing the
Setting Range
14
0 to 3, 14 to 17
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
If the PU is disconnected,
operation will be continued.
When the PU is
disconnected, an error is
displayed on the PU and the
inverter output is shut off.
Get other manuals https://www.bkmanuals.com
PU Disconnection
Detection
88
PARAMETERS
STOP
key.
RESET
PU Stop
Selection
STOP
Pressing the
RESET
key decelerates
the inverter to a
stop only in the
PU operation
mode.
STOP
Pressing the
RESET
key decelerates
the inverter to a
stop in any of the
PU and
DeviceNet
operation modes.
4