I/O SIGNAL LIST
6.2.3

I/O signal when CC-Link Ver.2 double setting is selected (Pr. 544 = 12)

(1) Remote I/O (32 points)
Same as when Pr. 544 = 0 (
(2) Remote resister
Description
Address
Upper 8 Bits
RWwn
Monitor code 2
Set frequency (0.01Hz increments) /
RWwn+1
torque command *
Link parameter
RWwn+2
expansion setting
RWwn+3
RWwn+4
Monitor code 3
RWwn+5
Monitor code 4
RWwn+6
Monitor code 5
RWwn+7
Monitor code 6
("n" indicates a value determined according to the station number setting.)
*
For the FR-A700 series, setting "3" or "5" in Pr.804 during torque control under real sensorless vector control or
vector control sets torque command in RWwn + 1.
48
Refer to page 44)
Refer
Lower 8 Bits
Page
Monitor code 1
Instruction code
Write data
to
Address
Upper 8 Bits
60
RWrn
60
RWrn+1
61
RWrn+2
Reply code 2
61
RWrn+3
61
RWrn+4
61
RWrn+5
61
RWrn+6
61
RWrn+7
Description
Lower 8 Bits
First monitor value
Second monitor value
Reply code 1
Read data
Third monitor value
Fourth monitor value
Fifth monitor value
Sixth monitor value
Refer
to
Page
64
64
64
64
65
65
65
65