Mitsubishi FR-E500 Series Instruction Manual page 181

Transistorized inverter
Hide thumbs Also See for FR-E500 Series:
Table of Contents

Advertisement

(8) Class 0x04 - Output Instance 100
Output
Byte
Instance
0
0x64
100
1
2
3
4
5
6
7
Data Name
Write Param
Net Ref
Net Ctrl
Fault Reset
MRS
Run Rev
Run Fwd
Speed
Reference
Acceleration
Time
Deceleration
Time
Bit 7
Bit 6
Bit 5
Write
Net
Net
Param
Ref
Ctrl
Speed Reference (Low Byte)
Speed Reference (High Byte)
Acceleration Time (Low Byte)
Acceleration Time (High Byte)
Deceleration Time (Low Byte)
Deceleration Time (High Byte)
1: The acceleration/deceleration time value is the value set with Byte
4, Byte 5, Byte 6 and Byte 7.
(As this is written while running, writing is enabled only when Pr. 77
is 2.)
0: The acceleration/deceleration time value is not written.
1: The speed reference is the value set with Byte 2 and Byte 3.
0: The speed reference is the value set from the parameter unit.
1: MRS, Fault Reset, Run Rev and Run Fwd are operated with
communications.
0: MRS, Fault Reset, Run Rev and Run Fwd are operated with the
inverter.
If Fault Reset makes a transition from 0 to 1 and there is an error in
the inverter, the inverter will reset.
1: The inverter output is shut off.
0: The inverter output shut off is canceled.
If Run Rev is 1 and Run Fwd is 0, runs in reverse direction.
If Run Fwd is 1 and Run Rev is 0, runs in forward direction.
Byte 2: Low-order byte of speed reference.
Byte 3: High-order byte of speed reference.
Byte 4: Low-order byte of acceleration time.
Byte 5: High-order byte of acceleration time.
(Acceleration time = Pr. 7)
Byte 6: Low-order byte of deceleration time.
Byte 7: High-order byte of deceleration time.
(Deceleration time = Pr. 8)
Get other manuals https://www.bkmanuals.com
Bit 4
Bit 3
MRS
0x00
Contents
163
Bit 2
Bit 1
Bit 0
Fault
Run
Run
Reset
Rev
Fwd