Zero Current Detection (Pr. 152, Pr. 153) - Mitsubishi FR-E500 Series Instruction Manual

Transistorized inverter
Hide thumbs Also See for FR-E500 Series:
Table of Contents

Advertisement

" " Zero current detection (Pr. 152, Pr. 153)

4.2.32 Zero current detection (Pr. 152, Pr. 153)
Pr. 152 "zero current detection level"
Pr. 153 "zero current detection period"
When the inverter's output current falls to "0", torque will not be generated. This may
cause a gravity drop when the inverter is used in vertical lift application.
To prevent this, the output current "zero" signal can be output from the inverter to close
the mechanical brake when the output current has fallen to "zero".
! If the output current remains lower than the Pr. 152 setting during inverter operation
for longer than the time set in Pr. 153, the zero current detection (Y13) signal is
output.
(Use Pr. 192 to assign the terminal used for Y13 signal output.)
Parameter
Factory
Number
Setting
152
153
Start signal
Pr. 152 "zero current
detection level"
Zero current
detection signal
output (Y13)
<Setting>
Refer to the following list and set the parameters:
Parameter
Number
Set the zero current detection level.
152
Set this parameter to define the percentage of the rated current at which the
zero current will be detected.
Set the zero current detection time.
153
Set a period of time from when the output current falls to or below the
Pr. 152 setting to when the zero current detection signal (Y13) is output.
Note: 1. If the current falls below the preset detection level but the timing condition is
not satisfied, the zero current detection signal is held on for about 100ms.
2. This function is also valid during execution of offline auto tuning.
3. When the terminal functions are changed using Pr. 192, the other functions
may be affected. Confirm the functions of the corresponding terminals before
making settings.
Setting
Range
5.0%
0 to 200.0%
0.5 s
0.05 to 1 s
OFF ON
Pr.152
OFF
Pr. 153 "detection time"
Get other manuals https://www.bkmanuals.com
Related parameters
Pr. 192 "A, B, C terminal
function (ABC) selection"
(Note)
Output current 0 [A]
100ms
OFF
ON
ON
Pr. 153 "detection time"
Description
114
PARAMETERS