INVERTER SETTINGS
3.3
Operation & Speed Command Source (Pr. 338, Pr. 339, Pr. 550)
(1) Select control source for NET mode (Pr. 550)
The control location for NET mode can be selected to be from either the inverter's RS-485 port or a
plug-on communication option card. Therefore, to control the inverter via the option card, Pr. 550 must
be set to either "9999" (default) or "0" (Communication option input valid).
Parameter
Name
Number
NET mode
operation
550
command source
selection
Refer to the inverter's user's manual (applied) for further details.
42
Default
Setting
Value
Range
Communication option card control is valid
0
(A7NETH-2P control is valid.)
Control via the inverter's RS-485 port
1
(A7NETH-2P control is invalid.)
Communication option automatic recognition.
9999
Normally, control via the inverter's RS-485 port
is valid. When an A7NETH-2P communication
9999
option card is installed, that communication
option card's control is made valid instead of
the inverter's RS-485 port.
Description