<Setting>
To make communication between the personal computer and inverter, the
communication specifications must be set to the inverter initially. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
Note: After making the initial setting of the parameters, always reset the inverter.
After
you
communication cannot be made unit the inverter is reset.
Parameter
Description
Number
Station
117
number
Communica-
118
tion speed
119
Stop bit length
Parity check
120
presence/
absence
Number of
121
communication
retries
Communica-
122
tion check
time interval
Waiting time
123
setting
CR • LF
instruction
124
presence/
absence
have
changed
the
Setting
Station number specified for communication from the
PU connector.
0 to 31
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
48
4800bps
96
9600bps
192
19200bps
0
Stop bit length 1 bit
8 bits
1
Stop bit length 2 bits
10 Stop bit length 1 bit
7 bits
11 Stop bit length 2 bits
0
Absent
1
Odd parity present
Even parity present
2
Set the permissible number of retries at occurrence
of a data receive error.
0 to 10
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an alarm stop.
If a communication error occurs, the inverter will not
come to an alarm stop. At this time, the inverter can
be coasted to a stop by MRS or RES input.
9999
During a communication error (H0 to H5), the minor
(65535)
fault signal (LF) is switched on. Assign the used
terminals with Pr. 192 "A, B, C terminal (ABC) function
selection".
0
No communication
Set the communication check time [seconds] interval.
If a no-communication state persists for longer than
0.1 to 999.8
the permissible time, the inverter will come to an
alarm stop.
9999
Communication check suspension
Set the waiting time between data transmission to
0 to 150
the inverter and response.
9999
Set with communication data.
0
Without CR/LF
1
With CR, without LF
2
With CR/LF
100