Related Constants
Name
Con-
stant
Display
Number
Reference
selection
b1-01
Reference
Source
Operation
method selec-
tion
b1-02
Run Source
Slave address
H5-01
Set the Inverter's slave address.
Serial Comm
Adr
Set the baud rate for MEMO-
Communica-
tion speed
BUS communications of com-
selection
munications connection
terminals.
H5-02
Serial Baud
Rate
Communica-
Set the parity for MEMO-
tion parity
BUS communications of com-
selection
munications connection
H5-03
terminals.
Serial Com Sel
Stopping
Set the stopping method for com-
method after
munications errors.
communication
error
H5-04
Serial Fault Sel
Communica-
Set whether or not a communica-
tion error detec-
tions timeout is to be detected as a
H5-05
tion selection
communications error.
Serial Flt Dtct
Send wait time
Set the time from the Inverter
H5-06
receiving data to when the
Transmit Wait-
Inverter starts to send.
TIM
RTS control
ON/OFF
H5-07
RTS Control
Sel
Description
Set the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal
(analog input)
2: MEMOBUS communications
3: Option board
4: Pulse train input
Set the Run Command input
method.
0: Digital Operator
1: Control circuit terminal
(sequence input)
2: MEMOBUS communications
3: Option board
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
0: No parity
1: Even parity
2: Odd parity
0: Deceleration to stop using
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-09
3: Continue operation
0: Do not detect.
1: Detect
Select to enable or disable RTS
control.
0: Disabled (RTS is always ON)
1: Enabled (RTS turns ON only
when sending)
Control Methods
Change
Setting
Factory
during
V/f
Range
Setting
Opera-
V/f
with
tion
PG
0 to 4
1
No
Q
Q
0 to 3
1
No
Q
Q
0 to 20
1F
No
A
A
*1
0 to 4
3
No
A
A
0 to 2
0
No
A
A
0 to 3
3
No
A
A
0 or 1
1
No
A
A
5 to 65
5 ms
No
A
A
0 or 1
1
No
A
A
Individual Functions
MEMO
Open
Open
BUS
Flux
Loop
Loop
Regis-
Vec-
Vector
Vector
ter
tor
1
2
Q
Q
Q
180H
Q
Q
Q
181H
A
A
A
425H
A
A
A
426H
A
A
A
427H
A
A
A
428H
A
A
A
429H
A
A
A
42AH
A
A
A
42BH
95
6-