Con-
stant
Number
Speed agree
detection
width
L4-02
Spd Agree
Width
Speed agree
detection
level (+/-)
L4-03
Spd Agree
Lvl+-
Speed agree
detection
width (+/-)
L4-04
Spd Agree
Width+-
Operation
when fre-
quency ref-
erence is
L4-05
missing
Ref Loss
Sel
Fault Restart: L5
User constants for restarting faults are shown in the following table.
Con-
stant
Number
Number of
auto restart
attempts
L5-01
Num of
Restarts
Auto restart
operation
selection
L5-02
Restart Sel
-64
5
Name
Description
Display
Effective when "Frequency
(speed) agree 1," "Desired fre-
quency (speed) agree 1," or
"Frequency (FOUT) detection
1," Frequency (FOUT) detec-
tion 2 is set for a multi-function
output.
Sets the frequency detection
width in Hz units.
Effective when "Desired fre-
quency (speed) agree 2," "Fre-
quency (FOUT) detection 3,"
or "Frequency (FOUT) detec-
tion 4" is set for a multi-func-
tion output.
Frequency that should be
detected is set in Hz units.
Effective when "Frequency
(speed) agree 2," "Desired fre-
quency (speed) agree 2," Fre-
quency (FOUT) detection 3 or
"Frequency detection 4" is set
for a multi-function output.
Frequency detection width is
set in Hz units.
0: Stop (Operation follows the
frequency reference.)
1: Operation at 80% speed
continues. (At 80% of speed
before the frequency
reference was lost)
Frequency reference is lost:
Frequency reference dropped
over 90% in 400 ms.
Name
Description
Display
Sets the number of auto restart
attempts.
Automatically restarts after a
fault and conducts a speed
search from the run frequency.
Sets whether a fault contact
output is activated during fault
restart.
0: Not output (Fault contact is
not activated.)
1: Output (Fault contact is
activated.)
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0.0 to
2.0 Hz
No
A
20.0
-400.0
to
0.0 Hz
No
A
+400.0
0.0 to
2.0 Hz
No
A
20.0
0 or 1
0
No
A
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 10
0
No
A
0 or 1
0
No
A
MEMO-
Open
Open
BUS
V/f
Loop
Flux
Loop
Regis-
with
Vec-
Vec-
Vec-
ter
PG
tor
tor
tor
1
2
A
A
A
A
49AH
A
A
A
A
49BH
A
A
A
A
49CH
A
A
A
A
49DH
MEMO-
Open
Open
BUS
V/f
Loop
Flux
Loop
Regis-
with
Vec-
Vec-
Vec-
ter
PG
tor
tor
tor
1
2
A
A
A
A
49EH
A
A
A
A
49FH
Page
6-51
6-52
6-52
6-72
Page
6-73
6-73