Con-
stant
Number
E2-11
E4-07
o2-04
b8-03
b8-04
C6-02
C6-11
E2-01
(E4-01)
E2-02
(E4-02)
E2-03
(E4-03)
E2-05
(E4-05)
E2-06
(E4-06)
E2-10
L2-02
L2-03
L2-04
L8-02
L8-39
N1-03
N5-02
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V Class
Inverters with outputs of 0.4 to 7.5 kW.
* 1. The initial settings for C6-02 are as follows: 0: Low noise PWM, 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, and 6: 15.0 kHz. If the
carrier frequency is set higher than the factory setting for Inverters with outputs of 5.5 kW or more, the Inverter rated current will need to be reduced.
* 2. This setting is for software versions PRG 1039 and earlier.
The carrier frequencies for the settings of C6-11 are as follows:
1: 2.0 kHz, 2: 4.0 kHz, 3: 6.0 kHz, 4: 8.0 kHz.
-94
5
Name
Unit
Inverter Capacity
Motor Rated Capacity
kW
2nd Motor Rated
Capacity
kVA selection
Energy-saving filter time
s
constant
Energy-saving coefficient
Carrier frequency selection
Carrier frequency selection
for open-loop vector 2 con-
*2
trol
Carrier frequency selection
upper limit
Motor rated current
A
Motor rated slip
Hz
Motor no-load current
A
Motor line-to-line resis-
Ω
tance
Motor leak inductance
%
Motor iron loss for torque
W
compensation
Momentary power loss
s
ridethru time
Min. baseblock (BB) time
s
Voltage recovery time
s
°C
Overheat pre-alarm level
Reduced carrier frequency
kHz
Hunting-prevention time
ms
constant
Motor acceleration time
s
Factory Setting
18.5
22
30
37
9
A
B
C
0.50 (Open-loop vector control)
57.87
51.79
46.27
38.16
6
4
4
4
4
4
2
2
6
6
4
4
65.8
77.2
105.0
131.0
1.67
1.70
1.80
1.33
15.7
18.5
21.9
38.2
0.101
0.079
0.064
0.039
20.1
19.5
20.8
18.8
505
538
699
823
2.0
2.0
2.0
2.0
1.0
1.1
1.1
1.2
0.6
0.6
0.6
0.6
90
90
95
100
2.0
2.0
2.0
2.0
10
10
10
10
0.317
0.355
0.323
0.320
45
55
75
90
D
E
F
10
2.00 (Open-loop vector control)
35.78
31.35
23.10
20.65
4
4
4
1
2
2
2
1
4
4
4
1
160.0
190.0
260.0
260.0
1.60
1.43
1.39
1.39
44.0
45.6
72.0
72.0
0.030
0.022
0.023
0.023
20.2
20.5
20.0
20.0
852
960
1200
1200
2.0
2.0
2.0
2.0
1.2
1.3
1.5
1.7
1.0
1.0
1.0
1.0
100
110
100
110
2.0
2.0
2.0
2.0
10
10
10
100
0.387
0.317
0.403
0.410
110
11
18.12
1
1
1
260.0
1.39
72.0
0.023
20.0
1200
2.0
1.7
1.0
110
2.0
100
0.580