Enter the motor nameplate data.
When the autotuning type has been selected, enter the motor information based on the motor nameplate data.
1
Press the Increment Key to display T1-02 (Motor Output Power).
2
Press the DATA/ENTER Key to display the current set value of T1-02.
Set the output power of the motor in kilowatts.
3
Press the Increment or Decrement Key to enter a numeric value.
Press the RESET Key to move the cursor to the digit to enter.
4
Press the DATA/ENTER Key to confirm the value.
Repeat steps 1 to 4 and enter the set values for the following user constants.
T1-03 (Motor Rated Voltage)
T1-04 (Motor Rated Current)
T1-05 (Motor Base Frequency)
T1-06 (Number of Motor Poles)
T1-07 (Motor Base Speed)
T1-08 (Number of PG Pulses when Turning): This user constant is only displayed for flux vector control.
Refer to Table 4.2 Constant Settings before Autotuning for details on the settings.