Pulse Train I/O: H6
User constants for pulse I/O are shown in the following table.
Con-
stant
Number
Pulse train
input func-
tion selec-
H6-01
tion
Pulse Input
Sel
Pulse train
input scal-
H6-02
ing
PI Scaling
Pulse train
input gain
H6-03
Pulse Input
Gain
Pulse train
input bias
H6-04
Pulse Input
Bias
Pulse train
input filter
time
H6-05
PI Filter
Time
Pulse train
monitor
selection
H6-06
Pulse Out-
put Sel
Pulse train
monitor
scaling
H6-07
PO Scaling
-58
5
Name
Description
Display
0: Frequency reference
1: PID feedback value
2: PID target value
Set the number of pulses in
hertz, taking the reference to be
100%.
Set the input gain level as a per-
cent when the pulse train set in
H6-02 is input.
Set the input bias when the
pulse train is 0.
Set the pulse train input pri-
mary delay filter time constant
in seconds.
Select the pulse train monitor
output items (value of the 
part of U1-).
There are two types of monitor
items: Speed-related items and
PID-related items.
Set the number of pulses output
when speed is 100% in hertz.
Set H6-06 to 2, and H6-07 to 0,
to make the pulse train monitor
output synchronously to the
output frequency.
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 2
0
No
A
1000 to
1440
Yes
A
32000
Hz
0.0 to
100.0%
Yes
A
1000.0
-100.0
to
0.0%
Yes
A
100.0
0.00 to
0.10
Yes
A
2.00
s
1, 2, 5,
20, 24,
2
Yes
A
36
0 to
1440
Yes
A
32000
Hz
MEMO-
Open
Open
BUS
V/f
Loop
Flux
Loop
Regis-
with
Vec-
Vec-
Vec-
ter
PG
tor
tor
tor
1
2
A
A
A
A
42CH
A
A
A
A
42DH
A
A
A
A
42EH
A
A
A
A
42FH
A
A
A
A
430H
A
A
A
A
431H
A
A
A
A
432H
Page
6-2
6-33
6-110
6-2
6-33
6-33
6-33
6-33
6-91
6-92