Vent Termination Clearances - England's Stove Works 55-TRPCB120 Installation & Operation Manual

Hide thumbs Also See for 55-TRPCB120:
Table of Contents

Advertisement

A) Min. 4‐ft clearance below or beside any door or window that opens. 
B) Min. 1‐ft clearance above any door or window that opens. 
C) Min. 2‐ft clearance from any adjacent building. 
D) Min. 7‐ft clearance from any grade when adjacent to public walkways. 
E) Min. 2‐ft clearance above any grass, plants, or other combustible materials. 
F) Min. 3‐ft clearance from a forced air intake of any appliance. 
G) Min. 2‐ft clearance below eaves or overhang. 
H) Min. 1‐ft clearance horizontally from combustible wall. 
I)   Vents installed with mechanical exhausters shall terminate not less than 12 in. (305mm) above the 
highest point where they pass through the roof surface. 
 
Notes on termination of Pellet Vent Pipe from NFPA 211 (2006 ed.) Section 10.4 Termination: 10.4.5  
 
(See also "INSTALLATION" section of manual AND additional notes above):
 Not less than three (3) feet above any forced air inlet located within ten (10) feet. 
 Not less than four (4) feet below, four (4) feet horizontally from, or one (1) foot above any door, 
window or gravity air inlet into any building. 
 Not less than two (2) feet from an adjacent building, and not less than seven (7) feet above grade 
where located adjacent to public walkways. 
The exhaust exit shall be arranged so that the flue gases are not directed so that it will affect people, overheat 
combustible structures, or enter buildings.  Forced draft systems and all parts of induced draft systems under positive 
pressure during operation shall be installed gastight or to prevent leakage of combustion products into a building.  
Through‐the‐wall vents shall not terminate over public walkways, or where condensate or vapor could create hazards 
IMPORTANT!  READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING CLEANING THE UNIT AS SPECIFIED, AND 
or a nuisance.   
ENGLAND'S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT, OR DUE TO UNSAFE INSTALLATION OR 
Be sure to follow local codes and all manufacturer's instructions (including exhaust pipe). 
Consult a professional installer and/or call Technical Support if you have any questions. 
 
 
VENT TERMINATION CLEARANCES 
 
REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED. 
USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH ANY QUESTIONS. 