England's Stove Works 55-TRPCB120 Installation & Operation Manual page 13

Hide thumbs Also See for 55-TRPCB120:
Table of Contents

Advertisement

INSTALLATION 
Approved Venting Method 3: Existing Chimney System 
 Using an existing masonry or factory built chimney for venting is the only other acceptable method 
for venting this pellet unit. 
installation. 
 When connecting to an existing masonry chimney, the cross‐sectional area of the flue must be 
considered.  A chimney with a flue larger than 6" round (28.27 sq. in.) may require relining with an 
approved pellet stove chimney lining system. 
 Use an appliance collar where the pellet vent connects to the exhaust output of the pellet stove 
and attach the appliance collar to the exhaust blower output using three sheet metal screws.  
 Seal each pipe connection joint with high temperature RTV Silicone, to ensure the system is leak 
free (Check with the specific pipe manufacturer's instructions before doing so). 
 If the pellet vent pipe being used is not a "Twist Lock" system, three (3) sheet metal screws are 
required at each pipe joint. 
 Connect the pellet stove to outside combustion air using the kit included with your stove or using 
an alternative method, as described in the "Outside Air" section, on page 15. 
 
Please Note: 
Installation diagrams are for reference purposes only and are not drawn to scale, nor meant to be used as plans for each individual 
installation.  Please follow all venting system requirements, maintain the required clearances to combustibles, and follow all local 
codes.
 
IMPORTANT!  READ AND FOLLOW ALL INSTALLATION AND MAINTENANCE INSTRUCTIONS, INCLUDING CLEANING THE UNIT AS SPECIFIED, AND 
ENGLAND'S STOVE WORKS IS NOT RESPONSIBLE FOR ANY DAMAGE OR INJURY INCURRED DUE TO NEGLECT, OR DUE TO UNSAFE INSTALLATION OR 
 
 
existing chimney.  Use the appropriately sized adapter when 
transitioning from the pellet vent pipe to the masonry or 
factory built thimble and be certain that the adapter is 
sealed tightly to both the pellet venting system and the 
existing chimney. 
good condition (A chimney sweep inspection is highly 
recommended).  Also, make sure the chimney meets the 
minimum standards listed in NFPA 211 (A chimney 
professional can confirm this upon inspection). 
may ONLY be a 6" flue, UL103 HT venting system (ULC S629 
if Canada).  Connection to any other factory built chimney 
may result in a poorly operating or dangerous stove 
REPLACING GASKETS ANNUALLY, AND PARTS AS NEEDED. 
USAGE OF THIS PRODUCT. CALL TECHNICAL SUPPORT WITH ANY QUESTIONS. 
Use Type L or Type PL venting pipe until entering the 
Before using an existing chimney, be certain it is in 
If connecting this stove to a factory built chimney, it 
13 
For high altitude installations 
(above 4,000 ft.), the vent pipe 
should be increased from 3‐inch 
(3") to four‐inch (4"). 

Advertisement

Table of Contents
loading

This manual is also suitable for:

55-shpcb12025-cb12025-ssp01

Table of Contents