Innocat0Stop; Indefaultoverload; Indefaulthybrid - Siemens SIMOCRANE Operating Instructions Manual

Energy storage system management v01.01
Table of Contents

Advertisement

Block interface
5.1 Inputs
5.1.10

inNoCat0Stop

This input can be used in addition to the "CAT-0" signal that is transferred via the remote control
(inReceiveFromMaster.ControlWord2.Bit2). A local stop signal is implemented in this way, e.g.
via hardware inputs.
• 0 = "CAT-0" stop request, shutdown routine 3 is triggered
• 1 = No "CAT-0" stop request
Table 5-30
Input
inNoCat0Stop
5.1.11

inDefaultOverload

This input can be used for configuring the "Bypass" function after startup of the ESS IF PLC:
• 0 = No Bypass
• 1 = Bypass
Table 5-31
Input
inDefaultOverload
5.1.12

inDefaultHybrid

This input can be used for configuring the "Hybrid" function after startup of the ESS IF PLC:
• 0 = No Hybrid
• 1 = Hybrid
Table 5-32
Input
inDefaultHybrid
50
inNoCat0Stop
Data type
Bool
inDefaultOverload
Data type
Bool
inDefaultHybrid
Data type
Bool
Comment
Use this input to specify whether
a local category 0 stop request is
active.
Comment
The system starts with this func‐
tion by default.
Comment
The system starts with this func‐
tion by default.
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE