Siemens SIMOCRANE Operating Instructions Manual page 110

Energy storage system management v01.01
Table of Contents

Advertisement

Diagnostic system
7.2 Warnings
Bit 12
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 13
-
Bit 14
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 15
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 16
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 17
Message class
Component
Response
108
Charge- /Discharge commands not plausible
Warning
Control
Charge/discharge commands are ignored
Self-acknowledging
Charge and discharge have been selected simultaneously
Check the control
Spare
-
Discharge power limited by DC/DC Converters
Warning
Power converter
Limitation of the discharge power to maximum power converter power
Self-acknowledging
Power converters are limiting the maximum discharge power
Check the power converters
Charge power limited by DC/DC Converters
Warning
Power converter
Limitation of the charge power to maximum power converter power
Self-acknowledging
Power converters are limiting the maximum charge power
Check the power converters
System overload blocked due to battery SOC limitation
Warning
Power converter
Overload operation not possible
Self-acknowledging
Battery almost fully charged or discharged
Change the battery to a valid SOC range
Overload capacity exhausted > 70 %
Warning
Power converter
None
SIMOCRANE Energy Storage System Management V01.01