Diagnostic system
7.3 Faults
Bits 2-31
-
7.3
Faults
7.3.1
Main
Bit 0
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 1
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 2
Message class
Component
Response
Acknowledgement
Cause
Remedy
114
Spare
-
Watchdog timeout Master PLC
Fault
PROFINET communication
Shutdown routine 3
ETechAcknowledge
•
I-Device communication between the master and the SIMOCRANE ESSM IF
PLC is interrupted
•
Incorrect hardware configuration
•
Watchdog interconnection in master PLC faulted
•
Check the communication parameters
•
Check the cabling
Critical parametrization error: SOC range battery
Fault
Parameterization
Shutdown routine 3
ETechAcknowledge
The parameterized battery SOC range is invalid
Enter a valid parameterization
Critical parametrization error: Voltage range battery
Fault
Parameterization
Shutdown routine 3
ETechAcknowledge
The parameterized voltage range is invalid
Enter a valid voltage range
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE