Diagnostic system
7.3 Faults
Bit 5
Acknowledgement
Cause
Remedy
Bits 6-31
-
7.3.12

Unit 7

Bit 0
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 1
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 2
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 3
Message class
Component
136
Unit Disconnected while running
ETechAcknowledge
Unit 6 was disconnected from the line supply during operation
Fuse tripped
Clarify the cause
Replace the fuse links if necessary
Spare
-
Unit CAT-0 Stop
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 3
ETechAcknowledge
Unit 7 has triggered an internal CAT-0 stop
Clarify the cause (see following messages)
Unit Fault present
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 3
ETechAcknowledge
Unit 7 has an internal fault
Clarify the cause (see following messages)
Unit Communication Fault
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 3
ETechAcknowledge
The communication connection to the unit is faulted
Check the network connection
Unit Line contactor failure
Fault
Internal SIMOCRANE ESSM Vx.x
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE