To Connect The Safety Thermostat (Normally Closed Contact) - Daikin EBVZ-D9W Installer's Reference Manual

Table of Contents

Advertisement

9
|
Electrical installation

9.3.9 To connect the safety thermostat (normally closed contact)

Installer reference guide
122
A
B
A
B
a Installation of EKRP1AHTA (+ mounting plate, see
4
plate" [
 128]) is required.
3 Fix the cable with cable ties to the cable tie mountings.
1 Open the following (see
1 Top panel
2 User interface panel
3 Upper switch box cover
Main zone
Wires: 2×0.75 mm²
2 Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.
5
4
3
2
1
5
4
3
1 2
X801M
A8P
a
"7.2.4 To open the indoor
"9.4 To install the mounting
4
unit" [
 65]):
1
ERLA11~16D + EBVZ16S18+23D
Daikin Altherma 3 R F
4P643604-1B – 2022.05
3